3-Phase Power Formula:
From: | To: |
The 3-phase power calculation determines the real power (in kilowatts) delivered by a three-phase electrical system. It accounts for voltage, current, and power factor, which represents the phase difference between voltage and current waveforms.
The calculator uses the 3-phase power formula:
Where:
Explanation: The formula calculates real power by accounting for all three phases and the phase angle between voltage and current.
Details: Power factor represents the ratio of real power to apparent power. A lower PF means more current is required to deliver the same amount of real power, increasing losses in the system.
Tips: Enter line-to-line voltage in volts, current in amperes, and power factor (typically 0.8-0.95 for industrial loads). All values must be positive with PF between 0 and 1.
Q1: What's the difference between kW and kVA?
A: kW is real power (what performs work), while kVA is apparent power (voltage × current). kW = kVA × PF.
Q2: Why use line-to-line voltage?
A: Most 3-phase systems are specified with line-to-line voltage (e.g., 480V, 208V), which is what's measured between any two phases.
Q3: What's a typical power factor value?
A: Resistive loads have PF=1, motors typically 0.8-0.9, and heavily inductive loads can be 0.5 or lower.
Q4: How does this differ from single-phase calculation?
A: Single-phase uses \( kW = (V \times I \times PF)/1000 \) without the \( \sqrt{3} \) factor.
Q5: Can I use this for DC power?
A: No, DC power is simply \( kW = (V \times I)/1000 \) as there's no phase angle or \( \sqrt{3} \) factor.