3-Phase Power Factor Formula:
From: | To: |
Power Factor (PF) is the ratio of real power (measured in watts) to apparent power (measured in volt-amperes) in an AC electrical system. For 3-phase motors, it indicates how effectively electrical power is being converted into useful mechanical work.
The calculator uses the 3-phase power factor formula:
Where:
Explanation: The equation calculates how much of the total power is being used to do actual work versus being wasted in the system.
Details: A high power factor (close to 1) indicates efficient power usage. Low power factor means more current is required to deliver the same amount of real power, leading to energy losses and potential utility penalties.
Tips: Enter real power in watts, line-to-line voltage in volts, and current in amperes. All values must be positive numbers. The calculator will return a value between 0 and 1.
Q1: What is a good power factor for motors?
A: Most 3-phase motors have a power factor between 0.85 and 0.95 at full load. Values below 0.85 may indicate problems.
Q2: How can I improve power factor?
A: Power factor correction capacitors can be installed to reduce reactive power and improve overall power factor.
Q3: Why is power factor important for utilities?
A: Utilities must supply both real and reactive power. Low power factor means they need to provide more current for the same real power, increasing infrastructure costs.
Q4: Does power factor vary with load?
A: Yes, power factor typically decreases as motor load decreases below rated capacity.
Q5: What's the difference between leading and lagging power factor?
A: Lagging power factor (common with motors) means current lags voltage. Leading power factor (with capacitors) means current leads voltage.