Convert kW to Amps (480V 3-Phase)

3-Phase Power Formula:

\[ I = \frac{kW \times 1000}{\sqrt{3} \times 480 \times PF} \]

kW
(0 to 1)

Unit Converter ▲

Unit Converter ▼

From: To:

1. What is kW to Amps Conversion?

This calculator converts kilowatts (kW) to amperes (A) in a 480V three-phase electrical system. This conversion is essential for electrical engineers, technicians, and designers to properly size wires, circuit breakers, and other electrical components.

2. How Does the Calculator Work?

The calculator uses the three-phase power formula:

\[ I = \frac{kW \times 1000}{\sqrt{3} \times V \times PF} \]

Where:

Explanation: The formula accounts for the three-phase power relationship and the power factor which represents the phase difference between voltage and current.

3. Importance of Power Factor

Details: Power factor is crucial in AC circuits as it represents the ratio of real power to apparent power. A lower power factor means more current is required to deliver the same amount of real power, leading to larger conductors and higher losses.

4. Using the Calculator

Tips: Enter power in kilowatts and power factor (typically between 0.8 and 1.0 for most industrial equipment). The power factor must be between 0.01 and 1.00.

5. Frequently Asked Questions (FAQ)

Q1: Why is the voltage fixed at 480V?
A: This calculator is specifically designed for 480V three-phase systems which are common in industrial and commercial applications in North America.

Q2: What is a typical power factor value?
A: Induction motors typically have 0.85 PF, fluorescent lights 0.9-0.95, and resistive loads 1.0. The default 0.85 is a common industrial average.

Q3: How does this differ from single-phase calculation?
A: Single-phase uses \( I = kW \times 1000 / V / PF \) without the \( \sqrt{3} \) factor, resulting in higher current for the same power.

Q4: What if my system is 400V or 600V?
A: You would need a different calculator or modify the formula by changing the voltage value accordingly.

Q5: Why is the result important for electrical design?
A: The calculated current determines wire size, circuit breaker rating, and other protection devices needed for safe operation.